FQ2A/FQ2V Free Range Type Pulse to Analog Converter
Brand: YokogawaThe FQ2A/FQ2V is a compact, front terminal connection type pulse-to-Analog converter that receives pulse-train signals and converts them into DC voltage or DC current signals proportional to the frequency.
Features- With built-in 12 V or 24 V power Supply for Pulse Transmitter Inputs
- Input pulse Types Include Current pulse, Voltage Pulse, Non-voltage Contact and Open Collector Contact
- I/O Range, Input Pulse Width and Low Cut Point Setting, Zero/Span Adjustment and I/O Monitoring Can be Made On-site, using the Optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
- Internal Filter Can be Set to Eliminate Chattering (In Cases Where the Input Frequency Range is Up to 100 Hz, The Pulse Width is 3 Milliseconds or More)
Specifications
Brand
Accuracy
- ± 0.2% of Span
Consumption
- 60 mA at 24 Vdc - Current Consumption (FQ2V)
- 90 mA at 24 Vdc - Current Consumption (FQ2A)
Duty Cycle
- 50 ± 30% when the Input is 100% - Duty Cycle for Input Pulse Width
Electrical Connectors
- M4 Screw Terminal
Enclosure, Body Material
- ABS Resin
Frequency
- 0 to 1,000 Hz
Humidity
- 5 to 90% Relative Humidity, Non-Condensing - Operating Humidity
Input
- Open Collector Contact
Input Signal
- -1 to 8 V - Low Level
- 12 Vdc ± 10% - Transmitter Power Supply
- 2-24 V - High Level
- 24 Vdc ± 10% - Transmitter Power Supply
- Contact Pulse
- Current Pulse
- Voltage Pulse
Insulation Resistance
- 100 MegaOhms or more at 500 Vdc between Input & Output, Output & Power Supply & Input, Power Supply
Mounting
- DIN Rail Mounting
- M4 Screw x 2 - Mounting Screw
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0-10 Vdc, Span is 0.5 V or more
- 0 to 100 mVdc, Span is 10 mV or more
- 0-20 mA DC, Span is 2 mA or more
- 0-5 mA DC - Span is 1 mA or more
- -10-10 Vdc
Power Supply
- 12 Vdc / 30 mA - Transmitter Power Supply
- 24 Vdc ± 10% (Percentage Ripple is 5% peak-to-peak or less)
- 24 Vdc / 30 mA - Transmitter Power Supply
Power Supply Effect
- ± 0.1% of Span or less for the Fluctuation within the Operating Range of Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations
Pulse Range
- 3 milliseconds or more - Pulse Width
Resistance
- 10 KiloOhms or more - Input Resistance (Contact or Voltage Pulse)
- 10 to 250 KiloOhms - Allowable Load Resistance
- 200 to 1,000 ohms (Selectable with Switch Inside) - Input Resistance (Current Pulse)
Response Time
- 2 Intervals of Input + 50 milliseconds, 63% Response (10 to 90%)
Span & Zero Adjustments
- ± 10% - Output Adjustment
Supply Voltage
- 1,500 Vac/minute between Input, Output & Power Supply - withstand Voltage
- 10 mV-20 V - Span (DC)
- 500 Vac/minute between Output & Power Supply - withstand Voltage
Temperature Effect
- ± 0.2% of Span or less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change
Zero Offset
- -100 to 200% - Zero Elevation