MS5D Dual Output Range Potentiometer Converter
Brand: YokogawaThe MS5D is a plug-in type potentiometer converter that is used in combination with an instrument to transmit information for displacement of valve etc. by resistance change of potentiometer.
It converts the resistance changes into isolated DC current or DC voltage signals.
Features- I/O Range Setting, Burnout Setting, Output Adjustment, I/O Monitoring, and Loop Back Test Can be Made Using the Optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
- The Operation Indicating Lamp Shows the Operation Status, Abnormalities in a Setting etc
- Adjustment (Input Range 0%, 100% Setting) of Combination with Potentiometer and Output Adjustment Can be Made Using the Switches on the Front Panel of the MS5D Without a Setting Tool Such as Handy Terminal
Specifications
Brand
Accuracy
- ± 0.1% of Span
Burn-Out
- Downscale
- Off
- Time: 60 seconds, Maximum
- Upscale
Consumption
- 2.2 W at 110 Vdc - Power Consumption
- 2.3 W at 24 Vdc - Power Consumption
- 4.6 VA at 100 Vac - Power Consumption
- 6.4 VA at 200 Vac - Power Consumption
Current
- 1-20 mA DC - Span
Electrical Connectors
- M3.5 Screw Terminal
Enclosure, Body Material
- ABS Resin
Humidity
- 5 to 90% Relative Humidity, Non-Condensing - Operating Humidity
Input
- Potentiometer Resistance Change (3-Wire Typical)
Insulation Resistance
- 100 MegaOhms at 500 Vdc between Input, Output, Power Supply & Grounding Terminals Mutually
Materials of Construction
- ABS Resin (Black), UL94 V-0 - Main Unit
- ABS Resin + Polycarbonate Resin (Black), UL94 V-0 - Main Unit
- Modified Polyphenylene Oxide Resin, Including Glass Fiber (Black), UL94 V-1 - Socket
- PBT Resin, Including Glass Fiber (Black), UL94 V-0 - Main Unit
Mounting
- DIN Rail Mounting
- Plug-in Typical
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Operating Voltages
- 12-48 V
- 85-264 V
Output Signal
- ± 10 Vdc, Span is 0.1 V or more
- ± 100 mVdc, Span is 10 mV or more
- 0-20 mA DC, Span is 5 mA or more
- 0-5 mA DC - Span is 1 mA or more
- -10 to 10 Vdc
- 15 V / Maximum
- 7 V / Maximum
Power Supply
- 100-240 Vac/dc (-15%, 20%), 50/60 Hz - Power Supply Input & Rated Voltage
- 15-40 Vdc (± 20%) - Power Supply Input & Rated Voltage
Power Supply Effect
- ± 0.1% of Span or less - Effect of Power Supply Voltage Fluctuations
Resistance
- 10 KiloOhms or more for ± 10 Vdc - Allowable Load Resistance
- 100 to 10,000 ohms - Total Resistance for Input Signal
- 150 ohms or less Per Wire - Allowable Leadwire Resistance
- 2 KiloOhms or more for ± 5 Vdc - Allowable Load Resistance
- 250 KiloOhms or more for ± 100 mVdc - Allowable Load Resistance
- 80 to 10,000 ohms (50% of Total Resistance or more) - Span for Input Signal
Response Time
- 150 milliseconds, 63% Response (10 to 90%)
Span & Zero Adjustments
- ± 5% of Span or more - Output Adjustment
Supply Voltage
- 1,000 Vac for 1 Minute between Output-1 & Output-2 - withstand Voltage
- 10 mV-20 V - Span (DC)
- 2,000 Vac for 1 Minute between Input, Output, Power Supply & Grounding - withstand Voltage
Temperature Effect
- ± 0.15% of Span or less at Change of 10° C (18° F) - Effect of Ambient Temperature Change
Zero Offset
- 50% of Resistance or less - Zero Elevation