WH5A/WH5V Isolator with Square Root Extractor
Brand: YokogawaThe WH5A/WH5V is a compact, front terminal connection type isolator that extracts the square roots of 1-5 Vdc signals and converts them into isolated DC current or DC voltage signals.
Features- Low cut point setting, zero/span adjustment, I/O monitoring, etc can be made using the optional parameter setting tool (VJ77) or handy terminal (JHT200)
- Dual output and 2,000 Vac withstand voltage specifications are available
Specifications
Brand
Accuracy
- ± 0.1% of Span
- within ± 0.2% - Relative Error between Output 1 & 2 (Dual Output)
Consumption
- 3 VA at 100 Vac - Power Consumption (WH5V)
- 4 VA at 100 Vac - Power Consumption (WH5A)
- 4.5 VA at 200 Vac - Power Consumption (WH5V)
- 5.5 VA at 200 Vac - Power Consumption (WH5A)
- 50 mA at 24 Vdc - Current Consumption (WH5V)
- 70 mA at 24 Vdc - Current Consumption (WH5A)
Electrical Connectors
- M4 Screw Terminal
Enclosure, Body Material
- ABS Resin
Humidity
- 5 to 90% Relative Humidity, Non-Condensing - Operating Humidity
Input
- ± 9 Vdc or less - Maximum
Input Signal
- 1-5 Vdc
Insulation Resistance
- 100 MegaOhms or more at 500 Vdc
Mounting
- DIN Rail Mounting
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0 to 100 mVdc
- 0 to 24 mA DC to Span
- 10 mV-20 V - Span (DC)
- -10-10 Vdc
- 1-24 mA DC - Span
Power Supply
- 100-240 Vac (-15%, 10%), 50/60 Hz - AC Drive
- 24 Vdc ± 10% - DC Drive
Power Supply Effect
- ± 0.1% of Span or less - Effect of Power Supply Voltage Fluctuations
Resistance
- 1 MegaOhm - Input Resistance During Power On
- 100 KiloOhms - Input Resistance During Power Off
- 2 to 250 KiloOhms or more - Allowable Load Resistance for DC Voltage Output
- 750 to 15,000 ohms or less - Allowable Load Resistance for DC Current Output
Response Time
- 200 milliseconds, 63% Response (10 to 90%)
Span & Zero Adjustments
- ± 1% - Input Adjustment
- ± 10% - Output Adjustment
Supply Voltage
- 1,500 Vac/minute - DC & AC Drive withstand Voltage
- 500 Vac/minute - DC Drive withstand Voltage
Temperature Effect
- ± 0.2% of Span or less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change
Zero Offset
- 0 to 200% - Zero Elevation (Output Current Signal)
- -100 to 200% - Zero Elevation (Output Voltage Signal)