WH1A/WH1V Isolator

Brand: Yokogawa

The WH1A / WH1V is a compact, front terminal connection type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage signals.
Features
  • Dual output and 2,000 Vac withstand voltage specifications are available

Specifications

Accuracy

  • ± 0.1% of Span
  • Relative Error between Output1 & 2 is within ± 0.2% - Dual Output

Consumption

  • 10 VA at 100 Vac - Power Consumption (WH1A)
  • 102 mA at 24 Vdc - Current Consumption (WH1A)
  • 6 VA at 100 Vac - Power Consumption (WH1V)
  • 80 mA at 24 Vdc - Current Consumption (WH1V)

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90% Relative Humidity, Non-Condensing

Input

  • ± 30 Vdc or less - Maximum

Input Signal

  • 0 to 150 mA DC
  • 10 mV-600 Vdc - Span
  • 100 μA-150 mA DC - Span
  • -300 to 300 Vdc

Insulation Resistance

  • 100 MegaOhms or more at 500 Vdc

Mounting

  • DIN Rail Mounting
  • M4 Screw x 4
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 0 to 24 mA DC
  • 10 mV to 20 V - Span (DC)
  • -10-10 Vdc
  • 1-24 mA DC for Span

Power Supply

  • 24 Vdc ± 10%
  • 85-264 Vac, 47 to 63 Hz

Power Supply Effect

  • ± 0.1% or less for Fluctuation within the Operating Range of Power Supply Voltage Specification

Resistance

  • 1 MegaOhm During Power On - Input Resistance for DC Voltage
  • 100 KiloOhms During Power Off - Input Resistance for DC Voltage
  • 100 to 1,000 ohms - Input Resistance for DC Current
  • 2 to 250 KiloOhms or more - Allowable Load Resistance for DC Voltage Output
  • 750 to 15,000 ohms or less - Allowable Load Resistance for DC Current Output

Response Time

  • 150 milliseconds, 63% Response (10 to 90%)

Span & Zero Adjustments

  • -5 to 5% - Zero Adjustment
  • 95 to 105% - Span Adjustment

Supply Voltage

  • 1,500 Vac/minute - AC & DC Drive withstand Voltage
  • 500 Vac/minute - DC Drive withstand Voltage

Temperature Effect

  • ± 0.2% of Span or less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change

Zero Offset

  • 0 to 200% - Zero Elevation (Current Signal)
  • 0 to 73% - Zero Elevation (Current Signal)
  • -100 to 200% - Zero Elevation (Voltage Signal)
  • -80 to 73% - Zero Elevation (Voltage Signal)
show more