AR Surge Arrester
Brand: YokogawaThe high-performance AR surge arrester absorbs the potential of an inductive lightning surge caused by a lightning discharge to protect electronic instruments. The plug-in arrester consists of a separable main unit and terminal block.
Features- Absorbs large surge voltages immediately.
- Simple circuit configuration and excellent adaptability to a distributed control system.
- Plug-in connection of the main unit with the terminal block, eliminating concerns about an open-circuit state even if the main unit is removed.
- Support JIS
- JIS C 5381-21 (category: C1,C2):
- AR-SA, AR-HA, AR-TC, AR-RT, AR-HP, AR-LP, AR-SP
- AR-SY, AR1-B2, AR1-D62
- JIS C 5381-1 (class Ⅱ):
- AR-PS, AR-PH, AR-PW
- JIS C 5381-21 (category: C1,C2):
Specifications
Brand
Communication
- BRAIN
- HART
Current
- ≤ 1 mA at 200/400/420 Vdc - Permissible Current Leakage
- ≤ 10 μA at 50/90/160 Vdc - Permissible Current Leakage
- ≤ 2 µA at 8/40 Vdc - Permissible Current Leakage
- ≤ 5 µA at 25/30/70/160 Vdc - Permissible Current Leakage
- 100 mA DC - Rated Current
- 2 A AC - Rated Current
- 20 A AC - Rated Load Current
Enclosure, Body Material
- Flame Deterrent ABS Resin
Humidity
- 5 to 90% Relative Humidity, Non-Condensing
Input Signal
- 0 to 100 mA DC
- RTD
- Thermocouples
Mounting
- DIN Rail
- JIS Class D Grounding
- M4 Screw
Operating Temperature
- -10° to 60° C (14° to 140° F)
Operating Voltages
- 140-280 Vac - Maximum
- 25-160 Vdc - Maximum
- 8-160 Vdc - Maximum
Resistance
- 33 ohms ± 10%
Response Time
- 3 Nanoseconds
- 5 Nanoseconds
Supply Voltage
- 100-800 V - Voltage Protection Level (Between Lines)
- 150-1,500 V - Voltage Protection Level (Between Ground)
- 20-1,200 V - Instrument Side Voltage Limit (Between Ground)
- 20-420 Vdc - Discharge Starting Voltage (Between Lines)
- 2-1,000 V - Instrument Side Voltage Limit (Between Lines)
- 30-420 Vdc - Discharge Starting Voltage (Between Ground)
Documentation
Product Manuals
- IM77M02B01-01EN.pdf 416 KB
- IM77M02B02-01EN.pdf 443 KB
- IM77M02B11-01EN.pdf 412 KB
- IM77M02B12-01EN.pdf 443 KB
- IM77M02B13-01EN.pdf 412 KB
- IM77M02C01-01EN.pdf 411 KB
- IM77M02D01-01EN.pdf 412 KB
- IM77M02E01-01EN.pdf 479 KB
- IM77M02G01-01EN.pdf 443 KB
- IM77M02G02-01EN.pdf 442 KB
- IM77M02G03-01EN.pdf 425 KB
- IM77M02P01-01EN.pdf 404 KB
- IM77M02P02-01EN.pdf 379 KB
- IM77M02Y01-01E.pdf 76 KB
- IM77M02Y02-01E 030.pdf 156 KB
- IMAR51-01 003E.pdf 70 KB