30031A Clamp-On Tester
Brand: Yokogawa
Specifications
- Leakage current measurement range from 3mA to 60A
- Diameter of measurable conductor: 40 mm max.
- Easier and clear display
Specifications
Brand
Accuracy
- ± (1% of Reading + 5-Digits)
- ± (5% of Reading + 5-Digits)
Approvals & Certifications
- CE
Approvals & Certifications
- EN 61010-2-032 Category III 300 V
Battery Life
- Approximately 90 Hours
Consumption
- 6 mW, Maximum
Current
- 3 mA Range: Displays 0.000 mA (Zero) when 0.010 mA < I - Zero Correction
- 3 mA-60 A - AC Current
- 3.270 mA - Maximum
- 30 A Range: Displays 0.00 A (Zero) when 0.05 A < I - Zero Correction
- 32.70 A - Maximum
- 32.70 mA - Maximum
- 60.6 A - Maximum
Display
- Bar Graph (32-Segments)
- LCD Display (Digital Reading 3,200 Counts)
External Magnetic Field Effect
- 0.0005% Typical Value (In Terms of the Magnitude of Current in Adjacent Wires)
Humidity
- 80% Relative Humidity or less (Non-Condensing)
Operating Temperature
- 0° to 50° C (32° to 122° F)
Power Requirement
- CR2032 Lithium Battery
Resolution
- 0.001 mA
- 0.01 A
- 0.01 mA
- 0.1 A
Supply Voltage
- 3.7 kVac for One Minute - withstanding Voltage
- 300 Vrms or less - Circuit Voltage
Temperature Coefficient
- 0 ≤ I ≤ 50 A: ± (0.08% of Reading / °C + 0.5-Digits / °C)
- 50.0 < I ≤ 60.6 A: ± (0.3% of Reading / °C + 0.5-Digits / °C)
Turn-Off Time
- Power Approximately: 10 minutes after the Last Switch Operation - Automatic Power-Off