FC0A Output Isolator

Brand: Yokogawa

The FC0A is a compact, front terminal connection type output isolator that receives 4 to 20 mA signals, and converts them into 4 to 20 mA or 10to 50 mA DC current signals.
Features
  • When a load circuit opens, input resistance increases rapidly to 32k or more so as to detect the open state through the input device

Specifications

Accuracy

  • ± 0.1% of Span (4-20 mA DC Outputs)
  • ± 0.3% of Span (10-50 mA DC Outputs)

Consumption

  • 60 mA at 24 Vdc - Current Consumption

Electrical Connectors

  • M4 Screw Terminal

Enclosure, Body Material

  • ABS Resin

Humidity

  • 5 to 90% Relative Humidity, Non-Condensing - Operating Humidity

Input

  • 40 mA or less - Maximum

Input Signal

  • 4-20 mA DC

Insulation Resistance

  • 100 MegaOhms or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply

Mounting

  • DIN Rail Mounting
  • Rack-Mounted
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 4-50 mA DC

Power Supply

  • 24 Vdc ± 10% (Percentage Ripple is 5% peak-to-peak or less)

Power Supply Effect

  • ± 0.1% or less for the Fluctuation within the Operating Range of Power Supply Voltage Specification

Resistance

  • 300 ohms or less (10 to 50 mA DC Outputs) - Allowable Load Resistance
  • 750 ohms or less (4-20 mA DC Outputs) - Allowable Load Resistance

Response Time

  • 150 milliseconds, 63% Response (10 to 90%)

Supply Voltage

  • 1,500 Vac/minute between (Input & Power Supply) & Output - withstand Voltage
  • 500 Vac/minute between Input & Power Supply - withstand Voltage

Temperature Effect

  • ± 0.2% of Span or less for a Temperature Change of 10° C (18° F) - Ambient Temperature Effect

Voltage Drop

  • 14 Vdc or less (10-50 mA DC Outputs)
  • 5 Vdc or less (4-20 mA DC Outputs)