FT5A/FT5V Free Range Type Thermocouple Converter
Brand: YokogawaThe FT5A/FT5V is a compact, front terminal connection type signal conditioner that is connected to an IEC/JIS-standard thermocouple (TC), such as a Type K, T, E, J, R, S, B or N thermocouples to convert temperature signals into isolated DC current or DC voltage signals.
Features- Selection of input type, input range setting, burnout setting, output adjustment, I/O monitoring, and loop back test can be made using the optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200)
- For the Fahrenheit display, specify the option “/DF”
- Available for the combination with Safety barrier (BARD-600)
Specifications
Brand
Accuracy
- ± 0.1% of Span
Approvals & Certifications
- IEC
Connection Style
- M4 Screw Terminal
Consumption
- 24 Vdc 65 mA (FT5A)
- 50 mA (FT5V)
Humidity
- 5 to 90% Relative Humidity Non-Condensing
Input
- 0.1 µA
- -0.5 to 4 Vdc
Insulation Resistance
- 100 MegaOhms at 500 Vdc
Load Impedance
- 750 to 250,000 ohms
Mounting
- DIN Rail
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0 to 100 mVdc
- 0-20 mA DC
- 0 to 24 mA DC
- -10 to 10 Vdc
Power Requirement
- 24 Vdc ± 10%
Power Supply Effect
- ± 0.1% of Span
Resistance
- 1 KiloOhm or less (Signal Source Resistance)
- 1 MegaOhm or more - Input Resistance
- 10 KiloOhms or more when Power Off (Input Resistance)
Response Time
- 200 milliseconds
Span & Zero Adjustments
- ± 1% of Span - Input Adjustment
- ± 10% of Span - Output Adjustment
Span Effect
- 10 mV-20 V
- 1-24 mA DC
Supply Voltage
- 1,500 Vac - withstand Voltage
Temperature Effect
- ± 0.2% of Span or less for a Temperature Change of 10° C (18° F)
Temperature Range
- -270° to 1,820° C (-454° to 3,308° F)
Zero Offset
- -100 to 200%